Facility Condition Index (FCI): what it measures, and how B³NMA calculates it
The FCI compares what a building needs in repairs with what it would cost to replace it. It is the most widely used single measure of building condition, and also one of the easiest to misread, because there is more than one way to calculate it.
Last reviewed September 25, 2026.
The ratio
FCI = cost to correct deficiencies ÷ current replacement value. A building with $400,000 of repairs and a replacement value of $10 million has an FCI of 4%. The lower the number, the better the condition.
The ratio was first published in 1991 by Sean C. Rush in Managing the Facilities Portfolio, for the National Association of College and University Business Officers (NACUBO), with a set of rating bands drawn from the client data of the time:
| Rating | FCI |
|---|---|
| Good | Under 5% |
| Fair | 5% to 10% |
| Poor | Over 10% |
Two things change the number without the building changing: what counts as a deficiency (only what is broken today, or also what will need renewal soon), and how the replacement value was estimated. That is why a report should always say which method it used.
The methods in B³NMA
Each project picks one method, and every screen and report for that project uses it and names it. These are the exact calculations.
Repair and renewal backlog ÷ current replacement value × 100
Percent, lower is better. Good up to 5%, fair up to 10%, poor up to 30%, critical above 30%.
The backlog is the estimated cost to correct every deficiency recorded in the assessment, whatever the component's condition.
This is the ratio most owners already report, so it is the one to use when you compare with past studies or other organizations.
Where it comes from: The ratio and the 5% and 10% bands come from Rush (1991). The critical band above 30% is B³NMA's addition.
(repairs in poor components + half of repairs in fair components) ÷ current replacement value × 100
Percent, lower is better, on the same bands as the standard FCI.
Repairs recorded against components in good condition are left out, so the index tracks the backlog that is actually urgent.
Where it comes from: A B³NMA weighting. The app labels it ASTM because it grew out of ASTM E2018 condition walkthroughs, but ASTM E2018 does not define this formula.
(backlog + renewal cost of components due within the horizon) ÷ current replacement value × 100
Percent, lower is better, on the same bands. Horizon of 3, 5, 10 or 20 years.
A component counts at its full replacement cost when its remaining useful life, or its planned action year, falls inside the horizon; otherwise only its recorded repairs count.
It answers the question a capital plan asks: not only what is broken today, but what will need money in the next few years.
Where it comes from: Calculated as described here. Other publications use the same name for similar forward-looking ratios; check the definition before you compare figures.
Replacement-value-weighted average of component condition scores: good 85, fair 65, poor 40
0 to 100, higher is better. Good from 85, fair from 70, poor from 55, critical below 55.
Useful when an owner reports condition as a score rather than a cost ratio. Components without a condition rating are left out.
Where it comes from: Modelled on the 0–100 Condition Index of BUILDER, the U.S. Army Corps of Engineers' sustainment management system. BUILDER computes its index from the type, severity and density of each recorded distress; B³NMA's version is a simpler score from the good, fair and poor ratings, so the two are not interchangeable.
10 × capital action cost inside the horizon ÷ replacement value
0 to 5 and above, lower is better. Good to 0.50, fair to 1.00, fair/poor to 2.50, poor to 5.00, critical above 5.00. Horizon of 5, 10 or 20 years.
Only repair and renewal actions count; studies, maintenance and modernization are left out. The window starts in the review year, and a renewal that falls due again within the window counts each time. Work dated before the review year that is not marked done is still owed, so it counts in the review year.
Where it comes from: Maben Consulting's own method, used in its building condition assessment reports. It needs action years on the components to be calculated.
By building system: the System Condition Index
An FCI tells you how much backlog a building carries; the System Condition Index shows which system is carrying it. For each system, B³NMA divides that system's backlog by the replacement cost of its components. Components are grouped by their UNIFORMAT II code:
| System | UNIFORMAT II |
|---|---|
| Structure | A Substructure, B10 Superstructure |
| Building Envelope | B20 Exterior Enclosure, B30 Roofing |
| Interior Finishes | C Interiors |
| Building Services | D Services |
| Equipment | E Equipment and Furnishings |
| Siteworks | G Building Sitework |
Components under F (special construction and demolition), and B components without a level-2 code, are reported as unclassified rather than assigned to a system by guesswork. The system backlogs and the unclassified bucket add up to the standard FCI's backlog exactly.
Try the methods side by side
The same building can land in a different band depending on the method. Move the inputs and compare.
Condition Index (BUILDER). BUILDER SMS-style Condition Index: good = 85, fair = 65, poor = 40, weighted by each component's replacement value. ≥85 good · ≥70 fair · ≥55 poor · below that critical. Higher is better; 100 means like-new.
13 components · equal replacement value · higher is better
Sources
- Sean C. Rush, Managing the Facilities Portfolio: A Practical Approach to Institutional Facility Renewal and Deferred Maintenance (NACUBO, 1991), as cited by APPA: Deferred Capital Renewal and Deferred Maintenance
- Facility condition index: definition and the Rush (1991) rating bands
- U.S. Army: DoD adopts Army Corps of Engineers BUILDER SMS standard for facility condition assessments
- ERDC-CERL Sustainment Management System (BUILDER)
See the FCI on real buildings
The live demo has six fictional buildings across all four condition bands